D54

From Wikipedia, the free encyclopedia

D54 is an analogue lighting communications protocol used to control stage lighting. It was developed by Strand Lighting in the late 70s and originally designed to handle 384 channels. Though more advanced protocols exist such as Digital MultipleX DMX (lighting), it is still widely used in larger venues such as London's West End theatres, and popular amongst technicians because all the levels can be "seen" on an oscilloscope. D54 is still supported, and is available on the latest Strand 500 series consoles alongside DMX (lighting).

[edit] History

One of the significant problems in controlling dimmers is getting the control signal from a lighting control unit to the dimmer units. For many years this was achieved by providing a dedicated wire from the control unit to each dimmer (analogue control) where the voltage present on the wire was varied by the control unit to set the output level of the dimmer. In about 1976, to deal with the bulky cable requirements of analog control, Strand's R&D group in the UK developed an analogue multiplexing control system designated D54 (D54 is the internal standards number, which became the accepted name). Originally developed for use on the Strand Galaxy (1980) and Strand Gemini (1984) control desks.

Although a claimed expansion capability of 768 dimmers was documented; early receivers used simple hardware counters that rolled over before reaching 768, effectively preventing commercial exploitation. The refresh period would also have been slow on such a long dimmer update cycle. Instead, multiple D54 streams were supported by some later consoles.

D54 was developed in the United Kingdom at approximately the same time as AMX192 (another analog multiplexing protocol) was developed in the United States, and the two protocols remained almost exclusively in those countries.

[edit] Protocol

Article Authors Note : Little information is available regarding this protocol, so the below data is unverified and provided 'as is'.

Electrical Parameters

Parameter Abr. Transmitting Receiving
Max Min Nominal Max Min Nominal
Transmitting Impedance1 Ro 10 Ω - - - - -
Receiving Impedance Ri - - - - 90 kΩ 100 kΩ
Termination per dimmer2 Rt - - - 30 kΩ 20 kΩ 24 kΩ
Termination capacitor3 Ct - - - +25% -25% 10 6 / Rt
Sync Level Vs -6.0 V -4.0 V -5.0 V - - -
Sync Detector Threshold Vst - - - -3.0 V -2.0 V -2.5 V
Full Level4 Vf 5.1 V 4.9 V 5.0 V 5.1 V 4.9 V 5.0 V
Off Level Vo 0.1 V 0.1 V 0.0 V 0.1 V 0.1 V 0.0 V
Safe Input Levels Vm - - - - +/-10 V -

1) Outputs to be short-circuit proof to 0 V to unlimited periods.
2) The termination resistor is paralleled for multiple dimmers received, e.g. 24 dimmers use 1 kΩ.
3) The termination capacitor is set to give a 1 µs time-constant, e.g. for Rt = 1k, Ct = 1,000 pF.
4) Full Level may be adjusted at the control system.

Temporal Parameters

Parameter Abr. Transmitting Receiving
Max Min Nominal Max Min Nominal
End of Frame pulse Te 0.5 s 35 µs - 0.5 s 30 µs -
Inter-Frame period Ti 15 µs 0.5 s - - 10 µs -
Sync Pulse Ts 10 µs 6 µs 8 µs 15 µs 3 µs -
Analogue Valid Delay Tv 15 µs - - 20 µs - -
Analogue Hold period Th Td 50 µs - Td 45 µs -
Total Dimmer period Td 0.5 s 70 µs - 0.5 s 70 µs -
Total Cycle period Tc 0.5 s - 40 ms 0.5 s - 40 ms
Analogue Gate Delay Tg 20 µs 0 - - - -
Number of Dimmers N 384 1 - 768 1 -
Slew Rate - - 2 V/µs 2.5 V/µs - 0 -


Signal/Timing diagram for Strand D54 dimmer control protocol
Signal/Timing diagram for Strand D54 dimmer control protocol